Read your meter's test LED
Electronic meters have a small LED on the face, often infrared, that blinks once for every fixed amount of energy. Meter shops use it to test accuracy. The amount per blink is the meter constant Kh, in watt-hours, printed on the faceplate (for example "Kh 1.0").
From blinks to watts
If blinks are t seconds apart, your power is:
watts = 3600 × Kh / tWith Kh 1.0, a blink every 3.6 seconds is 1,000 W. At low loads the blinks are minutes apart, so timing between blinks beats counting them.
Doing it
- A photodiode or phototransistor held over the LED on the outside of the glass, read by a microcontroller (an ESP32 is plenty) that timestamps each pulse.
- Shade it from daylight. If the LED is infrared, check that the sensor responds to it.
- Don't open the meter, break seals or touch the base. A sensor on the glass is enough.
The optical port
Many meters also have an ANSI C12.18 optical port: an infrared link a meter technician reads with a magnetic probe. It exposes the meter's C12.19 data tables, but utilities usually protect it with passwords. Treat it as the utility's tool, not a customer interface.